12

Recommended Coolants

Table 3

lists approved sources and recommended coolants with appropriate

corrosion inhibitors

for the drive loop:

Table 3

Recommended Drive Loop Coolants

Non-premixed coolants require a coolant-to-water mix ratio of 50% by
volume.

The estimated amount of coolant needed for Allen-Bradley 20L-LL*
Liquid-to-Liquid Heat Exchangers is 15.1 liters (4 gal). This coolant
estimate is based on the heat exchanger using 1.2 m (4 ft) hoses. Longer
hoses require more coolant. The maximum hose length of 9.1 m (30 ft)
would require up to an additional 2.8 liters (0.74 gal).

Important: Since coolant performance slowly degrades over time, the drive

loop coolant should be replaced every two years and/or
whenever the loop is drained for servicing.

Corrosion Inhibitor

If an approved coolant is not used, the drive coolant must consist of clean
water with a corrosion inhibitor. An approved corrosion inhibitor is
Chemtool, Inc. (www.chemtool.com) part number Watertool 4435-C. The
recommended concentration of the inhibitor is 8-10% by volume. Deionized
water is prohibited. Use distilled water or water with less than 50 ppm
concentrations of:

Sulfate and chloride

Hard water ions such as Mg++ and Ca++

Step 3

Connect the Cooling Loop

Drive Coolant Requirements

Source

Coolant Description

Interstate Chemical

http://www.interstatechemical.com/contact.htm

• NFP-50

(1)

, a 50/50 premix of propylene glycol and distilled water

• NFE-50

(1)

, a 50/50 premix of ethylene glycol and distilled water

Koolant Koolers/Dimplex Thermal Solutions

http://www.koolantkoolers.com/index.php/nic=contact

• K-Kool-E

(1)

, ethylene glycol (available premixed with distilled water)

• Propylene glycol

(1)

also available

Dow Chemical

http://www.dow.com

• Dowtherm

®

SR-1

(2)

, ethylene glycol

• Dowfrost

®

(2)

, propylene glycol

Dowtherm and Dowfrost are registered trademarks of the
Dow Chemical Company

(1)

Available in 5 gallon containers.

(2)

Not premixed with distilled water, and may not be available in 5 gallon quantities.

!

ATTENTION: Ethylene and propylene glycols must be
inhibited and silicate free. Use of common silicate-containing,
automotive-type ethylene glycol solutions is prohibited as they
may damage the heat exchanger and/or drive and cooling