PowerFlex 700L Frame 1X Drive Installation Instructions – Publication 20L-IN013A-EN-P – June 2009

37

• This check list supports the Basic Start-Up menu option. See

page 41

for

information on other start-up routines.

• A Human Interface Module (HIM) is required to run the Basic Start-Up

routine.

• The Basic Start-Up routine may modify parameter values for Analog and

Digital I/O. Refer to

Common I/O Programming Changes on page 45

.

1. Confirm that all inputs are connected to the correct terminals and are

secure.

2. Verify that AC line power at the disconnect device is within the rated

value of the drive.

3. Verify that control power voltage is correct.

4. The remainder of this procedure requires that a Human Interface Module

(HIM) be installed. Connect a HIM to Drive Peripheral Interface (DPI)
Port 2 (item 4 in

Figure 19 on page 44

). If an operator interface is not

available, remote devices should be used to start up the drive.

Important: When power is first applied, the HIM may require

approximately 5 seconds until commands are recognized
(including the Stop key). An explanation of the LED
indicators can be found on

page 44

.

5. Apply AC power and control voltages to the drive.

If any of the six digital inputs are configured to “Stop – CF”
(CF = Clear Fault) or “Enable,” verify that signals are present or
reconfigure [Digital Inx Sel], Parameters 361…366. If an I/O option is
not installed (that is, no I/O terminal block), verify that [Digital Inx Sel]
is not configured to “Stop – CF” or “Enable.” If this is not done, the drive
will not start. Refer to

Troubleshooting – Abbreviated Fault & Alarm

Listing on page 46

for a list of potential digital input conflicts.

If the STS LED is not flashing green at this point, refer to

Drive Status

Indicators and DPI Port Locations on page 44

.

6. When prompted, select a display language. The PowerFlex 700 Start-Up

Screen will then display.

Step 6

Start-Up Check List

!

ATTENTION: Power must be applied to the drive to perform
the following start-up procedure. Some of the voltages present
are at incoming line potential. To avoid electric shock hazard or
damage to equipment, only qualified service personnel should
perform the following procedure. Thoroughly read and
understand the procedure before beginning.

Prepare For Drive Start-Up