Step 6, Start-up check list, Prepare for drive start-up – Rockwell Automation 20L PowerFlex 700L Frame 1X Liquid-Cooled Adjustable Frequency AC Drive User Manual
Page 37
PowerFlex 700L Frame 1X Drive Installation Instructions – Publication 20L-IN013A-EN-P – June 2009
37
• This check list supports the Basic Start-Up menu option. See
for
information on other start-up routines.
• A Human Interface Module (HIM) is required to run the Basic Start-Up
routine.
• The Basic Start-Up routine may modify parameter values for Analog and
Digital I/O. Refer to
Common I/O Programming Changes on page 45
❏ 1. Confirm that all inputs are connected to the correct terminals and are
secure.
❏ 2. Verify that AC line power at the disconnect device is within the rated
value of the drive.
❏ 3. Verify that control power voltage is correct.
❏ 4. The remainder of this procedure requires that a Human Interface Module
(HIM) be installed. Connect a HIM to Drive Peripheral Interface (DPI)
Port 2 (item 4 in
). If an operator interface is not
available, remote devices should be used to start up the drive.
Important: When power is first applied, the HIM may require
approximately 5 seconds until commands are recognized
(including the Stop key). An explanation of the LED
indicators can be found on
❏ 5. Apply AC power and control voltages to the drive.
If any of the six digital inputs are configured to “Stop – CF”
(CF = Clear Fault) or “Enable,” verify that signals are present or
reconfigure [Digital Inx Sel], Parameters 361…366. If an I/O option is
not installed (that is, no I/O terminal block), verify that [Digital Inx Sel]
is not configured to “Stop – CF” or “Enable.” If this is not done, the drive
will not start. Refer to
Troubleshooting – Abbreviated Fault & Alarm
for a list of potential digital input conflicts.
If the STS LED is not flashing green at this point, refer to
Indicators and DPI Port Locations on page 44
.
❏ 6. When prompted, select a display language. The PowerFlex 700 Start-Up
Screen will then display.
Step 6
Start-Up Check List
!
ATTENTION: Power must be applied to the drive to perform
the following start-up procedure. Some of the voltages present
are at incoming line potential. To avoid electric shock hazard or
damage to equipment, only qualified service personnel should
perform the following procedure. Thoroughly read and
understand the procedure before beginning.
Prepare For Drive Start-Up