PowerFlex 700L Frame 1X Drive Installation Instructions – Publication 20L-IN013A-EN-P – June 2009

22

The PowerFlex 700L Frame 1X drive contains protective MOVs and
common mode capacitors that are referenced to ground. To guard against
drive damage and/or operation problems, these devices must be properly
configured according to

Table 7

.

Figure 7

MOV and AC EMI Capacitor Phase to Ground

Figure 8

Common Mode Capacitors to Ground

Table 7

Recommended Power Jumper Configurations

Disconnecting MOVs and Common Mode Capacitors

!

ATTENTION: The PowerFlex 700L Frame 1X drive contains
protective MOVs and common mode capacitors that are
referenced to ground. To guard against drive damage, these
devices must be disconnected if the drive is installed on an
ungrounded, impedance or phase-grounded distribution system.
See

Table 7

for recommended jumper configurations.

!

ATTENTION: PE-A, PE-B, and PE-C jumpers must be
configured according to the recommendations in

Table 7

. The

PE-D and PE-E power jumpers must always remain connected.

R/L1

S/L2

T/L3

1

2

3

4

PE–A

1

2

3

4

PE–C

DC+

DC–

PE–B

Power Source Type

(1)

MOV
(PE-A)

(2)

DC Bus
Common Mode
Caps (PE-B)

Input Filter
Caps (PE-C)

Bridge
Circuit Bd
Gnd (PE-D)

RTD Circuit
Bd Ground
(PE-E)

Benefits Of Correct
Configuration on Power
Source Type

Unknown

Connected

(3)

Disconnected

(3)

Connected

(3)

Connected

(3)

Connected

(3)

See below.

• AC fed Solidly Grounded
• DC fed from passive rectifier

which has a Solidly Grounded
AC source

Connected

Connected

Connected

UL compliance,
Reduced electrical noise,
Most stable operation,
EMC compliance,
Reduced voltage stress on
components and motor bearings

• AC fed Ungrounded
• Impedance Grounded
• DC fed from an active converter

Disconnected Disconnected

Disconnected

Helps avoid severe equipment
damage when ground fault
occurs

(1)

It is highly recommended to accurately determine the power source type and then configure appropriately.

(2)

When MOVs are disconnected, the power system must have its own transient protection to insure known and controlled voltages.

(3)

This is the factory default configuration. NOTE: The PE-D and PE-E power jumpers must be connected regardless of the power source type.