Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013

67

Appendix

B

HIM Parameters

This appendix provides information about the HIM parameters.

Besides the HIM, the following configuration tools can also be used to monitor
or change parameter values of the HIM, drive, and other connected peripherals:

Connected Components Workbench software, version 1.02 or later

DriveExplorer software, version 6.01 or later

DriveExecutive software, version 5.01 or later

Parameter List

Parameter

No.

Name and Description

Details

01

[Port Number]
Displays the port on the drive to which the HIM is connected.

Minimum:

1

Maximum:

7

Type:

Read Only

02

[DPI Data Rate]
Displays the DPI data rate at which the HIM is communicating with
the drive.

Values:

0 = 125 kbps
1 = 500 kbps

Type:

Read Only

03

[Initial Screen]
Selects the initial HIM screen to be displayed on power up.

Default:

0 = Status Scrn

Value:

0 = Status Scrn
1 = Process Scrn

Type:

Read/Write

Reset Required:

Yes

04

[Fault Dspy Type]
Selects the type of display flash to be shown when a drive or
peripheral fault is detected.

Default:

1 = Flash Status

Values:

0 = Flash Bklite
1 = Flash Status
2 = Flash None

Type:

Read/Write

Reset Required:

No

05

[Alarm Dspy Type]
Selects the type of display flash to be shown when a drive alarm is
detected.

Default:

1 = Flash Status

Values:

0 = Flash Bklite
1 = Flash Status
2 = Flash None

Type:

Read/Write

Reset Required:

No

06

[User Dspy Enable]
Enables/disables the HIM’s automatic user display time function,
which is configured using Parameter 07 - [User Dspy Time].

Default:

1 = Enable

Values:

0 = Disable
1 = Enable

Type:

Read/Write

Reset Required:

Yes

07

[User Dspy Time]
Sets the amount of time that a screen will remain displayed as long
as the HIM keys are not used. After this time elapses, the screen is
automatically replaced by the initial screen, which is selected
using Parameter 03 - [Initial Screen].

Default:

60 sec

Minimum:

10 sec

Maximum:

300 sec

Type:

Read/Write

Reset Required:

Yes