Using the HIM
Chapter 4
2.
Press the EDIT
soft key to display the edit pop-up box for the selected field
(in this case, the port number field).
3.
Use the
or
key to scroll to the port number of the device
whose parameter you want to target for the association (for this example,
Port 00, where the speed Reference parameters for the available drive ports
are located).
4.
Press the ENTER
soft key to enter the selected port number.
The target parameter selection pop-up box appears (see example screen
below), showing a list of available target parameters that can be associated.
5.
Use the
or
key to scroll to the target parameter you want to
associate.
For this example, we selected drive Parameter 877 - [Port 13 Reference]).
6.
Press the ENTER
soft key to enter the selected target parameter.
If the target parameter:
• Is not a bit parameter
, the parameter association is now changed and
the indirect selector or reference parameter screen re-appears with the
associated parameter information shown.
• Is a bit parameter
, a list of available bit numbers is displayed. Use the
or
key to scroll to the bit number of the target parameter
you want to associate, and press the ENTER
soft key. The parameter
TIP
The ‘Zero Speed’ setting may be available to select for specific
applications that require a safe-state speed Reference.
Stopped
0.00 Hz
AUTO
F
Edit Spd Ref A Sel
Select Port To Use
Zero Speed
Port 00 PowerFlex755
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
Edit Spd Ref A Sel
Select Param To Use
Par 0546
Spd Ref A Stpt
Par 0571Preset Speed 1
Par 0572 Preset Speed 2
ESC
ENTER
ESC
EDIT
Stopped
0.00 Hz
AUTO
F
#
Port 00 Dev Param 545
Spd Ref A Sel
P
00
P0871
Port
PowerFlex 755
PAR#