beautypg.com

Using direct numeric entry method – Rockwell Automation 20-HIM-C6S PowerFlex (Human Interface Module) User Manual

Page 54

background image

54

Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013

Chapter 4

Using the HIM

association is now changed and the indirect selector or reference
parameter screen re-appears with the associated parameter information
shown.

Using Direct Numeric Entry Method

1.

Access the indirect selector or reference parameter whose association you
want to change (for this example, drive Parameter 545 - [Spd Ref A Sel] as
shown below).

2.

With any field (port, parameter, or bit) selected, press the #

soft key to

display the Direct Numeric Entry pop-up box.

3.

Use the numeric keys to enter a number string that represents the target
parameter’s device port number, parameter number and, only when the
target parameter is a bit parameter, its bit number.

The number string format is PPpppp.bb, where:

PP = device port number
pppp = target parameter number
bb = bit number (only used when target parameter is a bit parameter)

4.

Press the ENTER

soft key to enter the number string and complete the

parameter association.

The indirect selector or reference parameter screen re-appears with the
associated parameter information.

ESC

EDIT

Stopped

0.00 Hz

AUTO

F

#

Port 00 Dev Param 545

Spd Ref A Sel

P

00

P0871

Port

PowerFlex 755

PAR#

ESC

EDIT

Stopped

0.00 Hz

AUTO

F

#

Port 00 Dev Param 545

Spd Ref A Sel

P

00

P0871

Port

PowerFlex 755

PAR#

Stopped

0.00 Hz

AUTO

F

Edit Spd Ref A Sel

871

0 << 159999

ESC

ENTER

This manual is related to the following products: