3 commissioning example, Commissioning example, 10 canopen option – Lenze E84DSxxx User Manual
Page 416

10
CANopen option
10.10
Monitoring
416
Lenze · 8400 protec StateLine · Reference manual · DMS 4.2 EN · 03/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
10.10.2.3 Commissioning example
Task
An 8400 controller (node 2) which is configured as heartbeat consumer is to monitor another 8400
controller (heartbeat producer, node 1).
• The heartbeat producer is to transmit a heartbeat telegram to the heartbeat consumer every
10 ms.
• The heartbeat consumer monitors the heartbeat telegram for arrival. A response is to be
activated in the event of an error.
Parameterising the heartbeat producer (node 1)
1. Set the heartbeat producer time (
) to 10 ms.
Parameterising the heartbeat consumer (node 2)
1. Set the CAN node address of the producer in
2. Set the heartbeat consumer time in
• Note: The heartbeat consumer time must be greater than the heartbeat producer time of the
node to be monitored set in
.
3. Set the desired response in
which is to be activated should a heartbeat event in the
consumer occur.
Tip!
displays the heartbeat status of the monitored nodes.
Heartbeat telegram
• The heartbeat telegram of the producer has the following identifier:
Identifier (COB-ID) = 1792 + producer's node address = 1792 + 1 = 1793 = 0x701
Note!
The heartbeat monitoring will not start until the first heartbeat telegram of a monitored
producer has been received successfully and the "Pre-Operational" NMT status has been
assumed.
The boot-up telegram counts as the first heartbeat telegram.