beautypg.com

Class1 FoamLogix 2.1A & 1.7AHP REV D User Manual

Page 50

background image

FoamLogix, Model 2.1A and 1.7AHP Class “A”

Electronic Foam Proportioning Systems

50

DO NOT PUMP WATER WITH THE HALE FOAM-

LOGIX FOAM PUMP FOR MORE THAN ONE (1)

MINUTE. DO NOT ATTEMPT TO CALIBRATE FOAM

PUMP FEEDBACK SENSOR WITH OTHER THAN

END USER SPECIFIED FOAM CONCEN TRATE.

MAKE SURE THE BYPASS VALVE IS IN THE

BYPASS POSITION WHEN PUMPING WATER

WITH THE FOAM PUMP.

1. Upon initial power-up with the foam tanks empty,

the display on the control unit alternates between

0

and

Lo A, indicating the foam tank is empty.

Fill the foam concentrate tank with WATER. The

Lo

A indication clears from the display, indicating the

low tank level sensor is operating properly.

2. Place the bypass valve to the

BYPASS position

to check foam pump operation. Place a calibrated

five gallon container at the discharge of the bypass

hose.

3. Place the system in simulated flow mode by

pressing the SELECT DISPLAY button

(

i ) until the LED under FLOW lights. Then

press both up  and down  buttons

simultaneously.

Set simulated flow value to

100 GPM by

pressing UP  or DOWN  button. The

display shows

S at the left most position to

indicate the simulated flow. (See Figure

24: “Simulated Flow Display.”)

4. Press the (

i ) button until the LED under %

FOAM lights. Set foam concentrate injection rate to

1.0 using the UP  or DOWN  button.

5. Cycle the (

i) button until the LED under TOTAL

FOAM lights. Press the ON button to energize the

Hale FoamLogix system.

Observe the discharge at the bypass hose to make

sure the foam pump is operating.

6. After one minute press the

ON button again to

STOP the foam pump. Approxi mately one gallon (3.8

liters) of water should discharge into the container.

The TOTAL FOAM display reads approximately

1.0.

7. Exit the simulated flow mode by selecting the

FLOW display and pressing both up  and down

buttons simultaneously.

8. Drain water from foam tanks and concen trate

lines and return the bypass valve to the

INJECT

position.

9. Verify operation of the flow sensor. Also calibrate

the flow sensor using the calibra tion procedures.

See heading “User calibration” beginning on page

53.

This completes the Hale FoamLogix system

operation checks accomplished at the system

installer facility.

Foam pump feedback calibration along with

setting of user specified default simulated flow and

concentrate injection rates should be accomplished

upon delivery to the end user using actual end user

specified foam concentrates and default values.

48

FOAMLOGIX, Model 2.1A Class "A"

Electronic Foam Proportioning System

Installation

ISO 9001 CERTIFIED

CAUTION! - continued

DO NOT PUMP WATER WITH THE HALE FOAM-

LOGIX FOAM PUMP FOR MORE THAN ONE (1)

MINUTE. DO NOT ATTEMPT TO CALIBRATE

FOAM PUMP FEEDBACK SENSOR WITH OTHER

THAN END USER SPECIFIED FOAM CONCEN-

TRATE.

MAKE SURE THE BYPASS VALVE IS IN THE

BYPASS POSITION WHEN PUMPING WATER

WITH THE FOAM PUMP.

1. Upon initial power-up with the foam tanks

empty, the display on the control unit

alternates between

0 and Lo A, indicating

the foam tank is empty.

Fill the foam concentrate tank with

WATER. The

Lo A indication clears from

the display, indicating the low tank level

sensor is operating properly.

2. Place the bypass valve to the

BYPASS

position to check foam pump operation.

Place a calibrated five gallon container at

the discharge of the bypass hose.

3. Place the system in simulated flow mode

by pressing the SELECT DISPLAY button

(

i) until the LED under FLOW lights. Then

press both up  and down  buttons

simultaneously.

Set simulated flow value to

100 GPM by

pressing UP  or DOWN  button. The

display shows

S at the left most position to

indicate the simulated flow. (See Figure

23: “Simulated Flow Display.”)

4. Press the (

i) button until the LED under %

FOAM lights. Set foam concentrate

injection rate to

1.0 using the UP  or

DOWN  button.

5. Cycle the (

i) button until the LED under

TOTAL FOAM lights. Press the ON button

to energize the Hale FoamLogix system.

Observe the discharge at the bypass hose

to make sure the foam pump is operating.

6. After one minute press the

ON button

again to STOP the foam pump. Approxi-

mately one gallon (3.8 liters) of water

should discharge into the container. The

TOTAL FOAM display reads approximately

1.0.

7. Exit the simulated flow mode by selecting

the

FLOW display and pressing both up 

and down  buttons simultaneously.

8. Drain water from foam tanks and concen-

trate lines and return the bypass valve to

the

INJECT position.

9. Verify operation of the flow sensor. Also

calibrate the flow sensor using the calibra-

tion procedures. See heading "User

calibration" beginning on page 51.

This completes the Hale FoamLogix system

operation checks accomplished at the system

installer facility.

Foam pump feedback calibration along with

setting of user specified default simulated

flow and concentrate injection rates should

be accomplished upon delivery to the end

user using actual end user specified foam

concentrates and default values.

Figure 24: Simulated Flow Display

This manual is related to the following products: