11. Trouble Shooting Guide
11.1 System
Diagnostics
Your DLC contains extensive diagnostics that allow it to determine the source of common problems. If
your DLC is not operating properly, your first course of action should be to review the
{DIAGNOSTICS} sub-menu in the {CONFIGURE} menu. To access this menu from the standard
operating mode follow this procedure (provided your user interface -- keypad and display -- is
functioning)]:
1. Press [MOTOR] repeatedly until the display reads {MOTOR OFF}.
2. Cycle power to the DLC (turn the main OFF then ON). This will cause the self-test routine to re-
execute.
3. Press [MENU]. The screen { - MENU - / DIAGNOSTICS-1} will appear. The value, in this case '1'
indicates how many failures were detected.
4. Press [ENTER] to enter the Diagnostics Menu. The screen {DIAG MENU 1/8 / POWER IN: OK}
will appear.
5. Repeatedly press [UP] to cycle through all eight Diagnostic screens.
6. If a screen displays a FAIL message, press [ENTER] to display the time and date the failure occurred.
Press [ENTER] again to display the clear screen. Press [UP] and then [ENTER] to clear the message.
Make a note of any failures reported in the Diagnostics Menu. Using this information, proceed with
the troubleshooting instructions below:
Other actions may be necessary to bring the process back to normal conditions before clearing a
failure.
MENU (DIAGNOSTICS)
Symptom
Probable Cause
Possible Solution
DIAG 1/11
POWER IN: FAIL
The power to the DLC-XP failed while the
pump motor was running.
Place DLC-XP in {MOTOR OFF} operating
mode before disconnecting power. See POWER
trouble shooting.
DIAG 2/11
ANALOG IN:
FAIL
The Analog Input signal fell outside of the
calibrated range, or fell to 0 within .25
seconds (i.e., the signal was changing by
more than 8.8mA per second and was less
than .3mA).
Place DLC in {MANUAL MODE} before the
signal loss occurs.
Re-calibrate Analog Input.
Condition Analog Input Signal.
See ANALOG INPUT trouble shooting.
DIAG 3/11
DIGITAL: FAIL
DIAG 4/11 LEAK
DET:
FAIL
The Leak Detection Switch closure
activated according to its configuration.
Review 7-General Operation: Leak Detection
Failure Set-up.
See LEAK DETECTION trouble shooting.
DIAG 5/11 LEVEL
SWITCH: FAIL
The Level Switch closure activated
according to its configuration.
Review 7-General Operation: Level Switch
Failure Set-up.
See DRUM LEVEL trouble shooting.
DIAG 6/11
MOTOR TEMP:
FAIL
DIAG 7/11 DRIVE
TEMP:
FAIL
The DLC internal temperature has
exceeded the units rating.
Re-locate the DLC to a environment with lower
ambient temperatures.
See 9-Specifications section.