6 digital output set up, 7 motor thermostat set up, 8 over temperature set up – Pulsafeeder Pulsar DLC XP RC User Manual

Page 41

background image

37

5. The display will then prompt for the motor status when the Level Switch input trips:

LEVEL SWITCH

MOTOR OFF? NO

Press [ENTER] if you DO NOT want the PULSAR motor to turn off when the input is sensed. Go to
step 7.

6. If you do want to the PULSAR motor to shut off is a low level is sensed, press [UP] to scroll to

{YES}. Press [ENTER].

LEVEL SWITCH

MOTOR OFF? YES

7. The display prompts you for the alarm relay status should Level Switch input trigger.

LEVEL SWITCH

ALARM RELAY? NO

Press [ENTER] if you do not want the Alarm Relay to activate with the Level Switch input. Go to
step 9.

8. If you want the Alarm Relay to activate with the Level Switch input, press the [UP] arrow key to

scroll to {YES}. Press [ENTER] to accept the setting.

LEVEL SWITCH

ALARM RELAY? YES

9. The display returns to the {MENU / DRUM LEVEL} screen.

7.2.6

Digital Output Set Up

This sub-menu is not functional with the NEMA 7 option.

7.2.7

Motor Thermostat Set Up

This sub-menu is not functional with the NEMA 7 option.

7.2.8

Over Temperature Set Up

This sub-menu allows you to disable the warning message when the DLC’s internal temperature
approaches it’s operating limit of 70

°C / 158°F. The error condition will not reset until the

temperature drops below 65

°C / 149°F. The difference between the trip and release point is 5°C /

9

°F.

1. Press [MENU] once and then [UP] seven (7) times until the display reads {– MENU – / OVER

TEMPERATURE}.

– MENU –

OVER TEMPERATURE

Press [ENTER] to go to the Over Temperature sub-menu.

2. The {OVER TEMPERATURE / ENABLED} (system default) screen is displayed.

OVER TEMPERATURE

ENABLED

3. Press [ENTER} to accept the {ENABLED} setting and you are returned to the {– MENU – / OVER

TEMPERATURE} screen.

or

Press [UP] to display the {OVER TEMPERATURE / DISABLED} screen.

OVER TEMPERATURE

DISABLED