7.2.17 Factory

Default

All of the DLC settings can be returned to factory defaults.

1. Press [MENU] and then [UP] sixteen times until the {MENU / FACTORY DEFAULTS} appears

flashing.

–MENU–

FACTORY DEFAULTS

Press the [ENTER] key to continue through the factory defaults sub-menu.

2. The display prompts you to not reset all the settings to the factory defaults.

FACTORY RESET?

NO

If this is not desired, press [ENTER] and go to step 4.

a) If the DLC should be reset to all factory defaults, use [UP] to scroll the value to {YES}.

FACTORY RESET?

YES

Press [ENTER] to accept.

3. The display double checks your action.

Re-setting Factory Defaults will destroy any user calibration information.


ARE YOU SURE?

NO

Use [UP] to change the value to {YES}. Press [ENTER] to accept the value.

4. The display returns to the menu for factory defaults.

7.3 Units

By pressing the UNITS button, the calibrated flow display will scroll through GPH, LPH, CCH, GPM,
LPM, CCM, or % stroke length setting. The DLC will automatically convert the flow rate, based on the
calibrated flow, to any of the above referenced units.

7.4

Varying The Flow Rate - Manually

The flow of the pump can be increased pressing [UP]. The flow rate can be decreased by pressing
[DOWN].

7.5 Mode

Pressing [MODE], switches the DLC–XP from MANUAL MODE, where the keypad is completely
functional to ANALOG MODE, where the DLC follows the analog input signal. This key acts like a
local auto/manual switch.

In the analog mode, the [MOTOR], [MENU] and [UNITS] keys are still operational on the keypad.