5 level switch failure set up – Pulsafeeder Pulsar DLC XP RC User Manual

Page 40

background image

36

4. The display prompts if the alarm relay should be triggered.

LEAK DETECTION

ALARM RELAY? NO

or

LEAK DETECTION

ALARM RELAY? YES

Press [ENTER] to accept the default of NO. If you want the alarm relay to active if a leak is detected,
press [UP] to scroll to {YES} and press [ENTER]. The display returns to the {MENU / LEAK
DETECTION} screen.

7.2.5

Level Switch Failure Set Up

This sub-menu allows the user to configure the DLC – XP to interact with a single point level sensor.
You can program one of the following responses:

− Shut the motor off,
− Trigger the alarm relay'
− Shut the motor off and trigger the alarm relay.


The level sensor must be a dry contact type. Refer to Section 5 – Installation: Low Voltage Input
Connections
.

1. Press the [MENU] key and [UP] four times until the {–MENU– / LEVEL SWITCH} screen is

displayed.

–MENU–

LEVEL SWITCH

Press [ENTER] to continue to program the Level Switch sub-menu.

2. The low level input can be configured as {INACTIVE}, if the system will not use a level sensor or as

{ACTIVE} if the system is going to use a level sensor.

LEVEL SWITCH

INACTIVE

Pressing [ENTER] when {INACTIVE} is displayed will cause the screen to return to the {–MENU–
/ LEVEL SWITCH} screen. Skip to step 9.

Pressing [UP] when {INACTIVE} is displayed will cause the screen to display {ACTIVE}.
Continue with step 3.

3. The low level input can be configured as {ACTIVE}, if the system will use a level sensor.

LEVEL SWITCH

ACTIVE

Pressing [ENTER] when {ACTIVE} is displayed will open the {LEVEL SWITCH / DRUM
LEVEL} screen.

LEVEL SWITCH

DRUM LEVEL

or

LEVEL SWITCH

START/STOP

Press [UP] to scroll to the next option {LEVEL SWITCH / START/STOP}

Press [ENTER] to make your selection and the following screen is displayed.

LEVEL SWITCH

NORMALLY OPEN

4. The input can be configured as {NORMALLY OPEN} by pressing [ENTER], or press [UP] to scroll

to the next input option (i.e., Normally Closed).

LEVEL SWITCH

NORMALLY CLOSED

Press [ENTER] to accept the desired configuration.