4 leak detection failure set up – Pulsafeeder Pulsar DLC XP RC User Manual

Page 39

background image

35

The display prompts the percent of flow as the default setting. Enter the new value using [UP]
and [DOWN]. Press [ENTER] to accept this value and the cursor moves to the next position.
Continue to use the arrow keys and press [ENTER] to accept your selections.

SIGNAL DEFAULT

000.0% FLOW

3. Pressing [ENTER] after configuring any of the previous steps (a-d) accepts your selection and will

additionally open an {ERROR MESSAGE / …..} screen.

ERROR MESSAGE

ENABLED

or

ERROR MESSAGE

DISABLED

Press [UP] or [DOWN] to select between ENABLED or DISABLED. Press [ENTER] to accept this
value. At this time the display is returned to the {–MENU– / ANALOG SIG FAIL} screen.

7.2.4

Leak Detection Failure Set Up

This sub-menu allows you to configure the DLC – XP to interact with a PULSAlarm Leak Detection
Diaphragm. You can modify the way the DLC – XP responds to the diaphragm rupture. The
following responses are available:

− Shut the motor off
− Trigger an alarm relay
− Shut the motor off and trigger an alarm relay.

Refer to Section 5 – Installation: Low Voltage Inputs for wiring information.

1. Press [MENU] to enter the {-MENU-} sub-system. Press [UP] three times until the {-MENU- /

LEAK DETECTION} is displayed. Press [ENTER] to continue to program the Leak Detection
options.

–MENU–

LEAK DETECTION

2. The Leak Detection Input can be configured as {INACTIVE}, if the pump is not supplied with a

PULSAlarm Leak Detection Diaphragm. Press [ENTER] to return to the screen {MENU / LEAK
DETECTION}.

LEAK DET INPUT

INACTIVE

a) Press [UP] to scroll to the next sub-menu. The Leak Detection Input relay can be configured as

{NORMALLY OPEN}.

LEAK DET INPUT

NORMALLY OPEN

or

b) Press [UP] to configure the relay as {NORMALLY CLOSED}.

LEAK DET INPUT

NORMALLY CLOSED

Press [ENTER] to accept the desired configuration.

3. The display prompts for you to configure the motor state (ON/OFF) should a diaphragm rupture

occurs (leak is detected).

LEAK DETECTION

MOTOR OFF? NO

or

LEAK DETECTION
MOTOR OFF? YES

Press [ENTER] to accept. If you do want to shut the motor off is a leak is detected, press [UP] to
scroll to {YES} and press [ENTER].