Setup Process

1. Navigate to the

CALIBRATION

menu, and scroll to the

MOTOR PARAM

option. The starting

display will be:

C A L I B R A T I O N
M O T O R P A R A M

2. Press the ENTER key

8 5

< 1 8 0 0 >

3. Use UP and DOWN arrows to adjust value as required, then press the ENTER key

8 6

< 1 . 2 >

4. Use UP and DOWN arrows to adjust value as required, then press the ENTER key

8 7

< 2 3 0 >

5. Use UP and DOWN arrows to adjust value as required, then press the ENTER key

8 8

< 6 0 >

6. Use UP and DOWN arrows to adjust value as required, then press the ENTER key

9 1

< 0 . 8 0 >

7. Use UP and DOWN arrows to adjust value as required, then press the ENTER key

8 1

E N T E R T O S T A R T

8. Press the ENTER key

C A L I B R A T I N G

9. The last screen will show

M O T O R P A R A M

c a l i b r a t e d

10. Upon completion of the routine, remove power from the MPC VECTOR controller for one minute,

and then re-apply power to complete the process.

After all of the Parameters have been entered, the drive needs to perform an auto-calibration routine
(Parameter 81). This calibration routine will take several seconds to complete. The user may use the Menu
Key to back up and/or out of the calibration any time prior to the auto calibration. The motor, and therefore
the pump, will not run during this auto-calibration procedure.