7.3 Analog Output Setup

No setup is required for the analog output. Analog output is always available at the corresponding terminals
(see wiring diagram Figure 4a, Section 5.3.4). The analog output follows and is proportional to motor speed.

7.4 Digital Output Setup

Each of the 3 Digital OUTPUTS can be selected as:

ON/OFF Status

AUTO/MAN Status

Leak Detected

Alarm Indicator

Tank Level Status


Each can be set as normally OPEN or normally CLOSED. For example, if an output is set to ON/OFF
INDICATION and NORMALLY CLOSED, this means that when the motor is running (indicator lamp is
ON) the output will be CLOSED. A NORMALLY OPEN setup will give the opposite response.

Digital output circuits are transistor based and limited to 40 VDC maximum, see Section 5.3.4, Input/Output
Signal Wiring
, and Section 11, Specifications, for more information).