Pulsafeeder MPC Vector User Manual
Page 32
26
8.2.2 “DRY” Analog Input Calibration
(keypad only, no signal present)
1. The starting display will be:
S E T P T
X X . X X X
F L O W
X X . X X X
2. Press the MENU key
- M E N U -
C A L I B R A T I O N
3. Press the ENTER key
C A L I B R A T I O N
P U M P F L O W
4. Press the UP arrow key twice, to access the analog input calibration
C A L I B R A T I O N
A N A L O G I N P U T
5. Press the ENTER key
A N A L O G I N P U T
W E T C A L
6. Press the UP or DOWN key
A N A L O G I N P U T
D R Y C A L
7. Press the ENTER key to access the DRY Pump Flow Calibration routine for ANALOG Flow Meters. A
blinking cursor will show you that you are adjusting the Current (mA).
M I N S E T P T 0 . 0 M A
F L O W : 0 . 0 0 G P M
8. Press the UP and/or DOWN keys to adjust the Current setpoint.
M I N S E T P T 4 . 0 M A
F L O W : 0 . 0 0 G P M
9. Press the ENTER key to accept this setpoint. The Cursor will now blink on the second line, indicating that
the 4mA Flow is the active field. Press the UP and/or DOWN keys to adjust the Flow setpoint.
M I N S E T P T 4 . 0 M A
F L O W : 0 . 0 0 G P M
10. Press the ENTER key to access the MAX setpoint values. The cursor will blink on the top line indicating
that the Current setpoint may be adjusted.
M A X S E T P T 1 6 . 0 M A
F L O W : 4 . 0 0 G P M