Calibrations, 1 pump flow calibration – Pulsafeeder MPC Vector User Manual

Page 26

background image

20

8. Calibrations

As a convention in this manual:

“WET” calibrations

will refer to those that require normal operating conditions, for example the

pump running with fluid, or an electrical signal input provided at the appropriate terminals.

“DRY” calibration

routines are run under other conditions, and often do not require the pump to run

or that a specific input signal be present.

Some of the calibration routines may be performed either way. Note any system requirements listed
for each routine.

8.1 Pump Flow Calibration

Pump flow calibration is not necessary for the standard speed controller. It is only necessary for models
configured for flow meter feedback. The selected flow meter should meet or exceed requirements listed in
the Flow Meters section (ref. Section12 - Specifications). The flow meter should also be calibrated prior to
MPC VECTOR calibration according to manufacturer specifications.

Y

OUR

MPC

VECTOR

IS NOT FACTORY CALIBRATED AS THE CALIBRATIONS ARE SYSTEM

DEPENDENT AND FLOW METER DEPENDENT

.

Y

OU MUST ALWAYS PERFORM A CALIBRATION WITH

THE

MPC

VECTOR

INSTALLED IN YOUR SYSTEM PRIOR TO USE

.

F

AILURE TO PROPERLY

CALIBRATE THE UNIT MAY RESULT IN DAMAGE TO SYSTEM COMPONENTS

.

The pump may be calibrated in WET (under normal operating conditions) or DRY (performed with pump
off) conditions.

8.1.1 WET Flow Calibration

The Wet Flow Calibration routine will require that the user turns on the pump. The flow meter should be
configured and calibrated prior to MPC VECTOR calibration (refer to flow meter IOM for calibration
instructions

). Please note that it must be safe to run the pump and dispense liquid into the system in order to

complete this calibration. The pump should be fully primed with the product in order to complete an
accurate calibration.

1. Press the MENU key to access the Calibration Menu.

- M E N U -

C A L I B R A T I O N

2. Press the ENTER key to access Pump Flow Calibration screen.

C A L I B R A T I O N

P U M P F L O W

3. Press the ENTER key to access Wet Pump Flow Calibration screen.

P U M P F L O W

W E T C A L

4. Press the ENTER key to begin Flow Calibration

C A L S P E E D

R P M 0