39

Param.

Name

Description

Range

Typical

Note

85

Motor Rated Speed

Nameplate RPM Rating

300 – 65,000
RPM

1800 RPM

86

Motor Rated Amps

Nameplate FLA Rating

0.0 – 480 Amps

Various

1

87

Motor Rated Volts

Nameplate Voltage Rating 0 – 600 Volts

230 VAC

88

Motor Base Frequency Nameplate Frequency

25 – 500 Hz

50 or 60 Hz

91

Motor Cosine Phi

Nameplate Cosine Phi

0.4 – 0.99

Approx 0.8

2

81

Invoking this parameter begins the auto-calibration routine

NOTES:

1. FLA = Full Load Amps

2. The Cosine Phi is also known as the Power Factor, this will sometimes be on the nameplate as

“PF”. If the Power Factor is given as a %, always use the decimal equivalent (for example a power
factor of 84% would be entered as 0.84) If the Cosine Phi is not provided by the motor manufacturer,
one of the following formulas may be used.

732

.

1

746

)

2

(

sin

cos

)

1

(

1

Ч

Ч

Ч

Ч

=

Φ





=

Φ

Current

Motor

Voltage

Motor

Efficiency

Motor

HP

Motor

COS

Current

Motor

Current

g

Magnetizin

COS

After all of the Parameters have been entered, the drive needs to perform an auto-calibration routine
(Parameter 81). This calibration routine will take several seconds to complete. The user may use the Menu
Key to back up and/or out of the calibration any time prior to the auto calibration. The motor, and therefore
the pump, will not run during this auto-calibration procedure.