Pulsafeeder MPC Vector User Manual
Page 31
25
10. Press the ENTER key once more to accept the calibration value
A P P L Y M A X M A
E N T E R T O S T A R T
11. Apply your desired maximum mA control signal to the MPC VECTOR (usually 20 mA)
12. Press the ENTER key
M A X S E T P T 2 0 . 2 M A
F L O W 7 . 0 1 G P M
(The mA value will be equal to your input signal level)
(The lower line shows the setting the MPC VECTOR will use for this signal value)
13. Press the UP and DOWN arrows to adjust the Speed/Flow corresponding to the Analog Input value.
14. Press the ENTER key once more to accept the calibration value
A N A L O G I N P U T
C A L I B R A T E D
15. Analog input signal calibration is complete
16. Press the MENU key three times to exit back to the main operating screen.
If you receive the following message:
C U R R E N T D E L T A
O U T O F R A N G E
This indicates that there is not a wide enough range between your maximum and minimum analog signals.
The minimum signal range is 3 mA. The most likely source of this error is the user did not change the value
of the incoming analog signal when moving from the MIN calibration to the MAX calibration.
The analog input signal calibration procedure should be performed again, ensuring that a minimum
of 3 mA difference exsists between the MIN and MAX signal levels.