21

5. Using the UP and/or DOWN arrow keys adjust the motor speed to approximate setpoint. This speed is just

a reference point for the MPC MPC VECTOR to measure flow meter input. If the maximum motor speed
for a given application is known, it is best to use this as a flow calibration point.

C A L S P E E D

R P M 1 8 0 0

6. Press the ENTER key to accept the calibration speed.

S T A R T M O T O R

Y E S = E N T R N O = M E N U

7. Press the ENTER key to start the motor and advance to the flow entry screen. You cannot start the motor

with the motor key during MENU operations.

P U M P F L O W

F L O W : 0 0 0 . 0 0 G P M

T

HE MOTOR WILL START WHEN THE ENTER KEY IS PRESSED

.

MAKE SURE THAT YOUR SYSTEM IS

PREPARED FOR OPERATIONS BEFORE STARTING THE MOTOR

.

8. Obtain flow rate from flow meter.

Pay close attention to the units used for flow rates. The flow rate entered into the MPC VECTOR
calibration MUST match the units displayed on the MPC VECTOR. You may back out of this
calibration routine at this time and change the MPC VECTOR flow units, if necessary.

9. Enter the flow rate from your flow meter. If flow meter output is not visually available you may obtain

flow rate through measurements and stopwatch. The UP and DOWN arrow keys may be used to change
each digit. Press the ENTER key after each digit has been entered to advance to the next digit or the
MENU key to back up.

P U M P F L O W

F L O W : 0 0 4 . 8 0 g p m

The calibration routine may be exited at any time prior to pressing ENTER after the last digit has been
entered by pressing the MENU key (several times) to back out. If there is a problem with flow units or
flow meter calibration back out before completing MPC VECTOR calibration and fix the problem.

10. Once all digits have been entered and the ENTER key is pressed, the WET flow calibration routine is

complete and you should see the following screen.

P U M P F L O W

C A L I B R A T E D

After the ENTER key has been pressed it will take several seconds for the calibration routine to
complete.

11. Pump flow calibration is complete.

12. Press the MENU key three times to exit back to the main operating screen.