Pulsafeeder MPC Vector User Manual
Page 28
22
8.1.2 DRY Flow Calibration
The DRY Flow Calibration routine does not require the pump to run. Instead, the user may input known
flow meter feedback values. This process can be used for fine adjustment of flow rate display, or in
situations where it is not possible or not safe to run the pump during calibration.
The DRY Flow Calibration Routine may be used to make small adjustments to the MPC VECTOR
calibration to ensure to make the MPC VECTOR display more closely matches the Flow Meter display.
If you are not using a flow meter for feedback, the DRY flow calibration routine can be used, but will
display motor RPM instead of mA value during the procedure.
1. Press the MENU key to access the Calibration Menu.
- M E N U -
C A L I B R A T I O N
2. Press the ENTER key to access Pump Flow Calibration screen.
C A L I B R A T I O N
P U M P F L O W
3. Press the ENTER key to access Wet Pump Flow Calibration screen.
P U M P F L O W
W E T C A L
4. Press the UP or DOWN key to access DRY Pump Flow Calibration screen.
P U M P F L O W
D R Y C A L
5. Press the ENTER key to access the DRY Pump Flow Calibration routine. A blinking cursor will show you
that you are adjusting the Current (mA).
M I N S E T P T 0 . 0 M A
F L O W : 0 . 0 0 G P M
6. Press the UP and/or DOWN keys to adjust the Current setpoint.
M I N S E T P T 4 . 0 M A
F L O W : 0 . 0 0 G P M
7. Press the ENTER key to accept this setpoint. The Cursor will now blink on the second line, indicating that
the Flow is the active field. Press the UP and/or DOWN keys to adjust the Flow setpoint.
M I N S E T P T 4 . 0 M A
F L O W : 0 . 0 0 G P M
8. Press the ENTER key to access the MAX setpoint values. The cursor will blink on the top line indicating
that the Current setpoint may be adjusted.
M A X S E T P T 1 6 . 0 M A
F L O W : 4 . 0 0 G P M