9 factory re-initialization – Pulsafeeder MPC Vector User Manual
Page 23
17
6.9 Factory Re-Initialization
Factory Re-initialization is typically not required. When re-initializing your MPC VECTOR, all of the
system settings and calibration information will be overwritten by the original factory default settings.
The controller must be re-configured and re-calibrated to your specifications.
A Factory Re-initialization should be performed only if there is reason to believe that the MPC VECTOR is
operating abnormally. The condition usually manifests itself with inconsistent or erratic operation – often
associated with meaningless characters on the display, or exaggerated numerical values. Commonly, a user
has entered incorrect parameters, or made changes to the setup of the control.
Once a re-initialization has been performed, all operating parameters should be checked and adjusted or re-
entered as necessary, including maximum flow and rpm, motor parameters, flow and analog signal
calibrations, etc.
Factory Re-Initialization:
1. Press the MENU key to access the System Setup Menu
- M E N U -
C A L I B R A T I O N
2. Press the UP arrow key to display
- M E N U -
S Y S T E M S E T U P
3. Press the ENTER key
S Y S T E M S E T U P
S T A T U S
4. Press the UP arrow key twice
S Y S T E M S E T U P
F A C T O R Y I N I T
5. Press the ENTER key
P R E S S E N T E R
T O F A C T O R Y I N I T
6. Press the ENTER key
A R E Y O U S U R E ?
Y E S = E N T E R N O = M E N U
7. Pres the ENTER key
R E S E T T I N G P U M P
T O F A C T O R Y I N I T