37

6. Press the ENTER key

S Y S T E M S E T U P

S T A T U S

7. Press the DOWN key five (5) times

S Y S T E M S E T U P

F L O W S E N S O R

8. Press the ENTER key to enter the Flow Sensor setup menus.

F L O W S E N S O R
S E N S O R T Y P E

9.

Press the ENTER key to see the current sensor configuration

.

S E N S O R T Y P E

I N A C T I V E

10. Press the ENTER key to change the sensor type.

S E N S O R T Y P E

< I N A C T I V E >

11. Press the UP arrow key until the analog flow meter option is displayed.

S E N S O R T Y P E

< A N A L O G >

12. Press the ENTER key to accept the new configuration.

S E N S O R T Y P E

A N A L O G

13. Press the MENU key several times to return to the Main screen.
14. Perform either a WET or DRY Flow Calibration on your MPC VECTOR (see Section 8.1: Pump Flow

Calibration).

15.

Your MPC MPC VECTOR is now ready for use with your flow meter.