Modifying the Sampling Interval, when Flow Meter feedback is used

1. The starting display will be:

S E T P T

X X . X X X

F L O W

X X . X X X

2. Press the MENU key

- M E N U -

C A L I B R A T I O N

3. Press the UP arrow key

- M E N U -

S Y S T E M S E T U P

4. Press the ENTER key

S Y S T E M S E T U P

S T A T U S

5. Press the DOWN key until you get to the PID screen

S Y S T E M S E T U P

P I D P A R A M E T E R S

6. Press the ENTER key

P I D P A R A M E T E R S

C O E F F I C I E N T S

7. Press the UP arrow key

P I D P A R A M E T E R S

S A M P L I N G P E R I O D

8. Press the ENTER key

S A M P L I N G P E R I O D

P E R I O D : X X X M S

9. Press the UP and/or DOWN arrows to adjust the sampling period, t

s

S A M P L I N G P E R I O D

P E R I O D : X X X M S

10. Press the ENTER key to accept the new sampling period

P I D P A R A M E T E R S

S A M P L I N G P E R I O D

11. The new PID sampling period has been set.