State of charge – Outback Power Systems MATE2 System Controller and Display Installation and User Manual User Manual
Page 93

93
ADV/MATE/AGS/MR---------------
end of MUST
RUN menu
UP TOP AGS
ADV/MATE/AGS/PG2-----------------
choose category
LOAD MUST
PG1 START RUN PG3
ADV/MATE/AGS/PG3----------------
choose category
%SOC
PG2 START TIMERS PG4
To proceed to the ADV/MATE/AGS/PG2 screen,
press the
Press the
AGS/PG3 screen which includes the EXERCISE
option.
Press the
With a FLEXnet DC, a user can start a generator
based on a battery state of charge rather than its
voltage, which can be less accurately inteprepeted
depending on loads and surges. Use the
and
A user can stop a generator based on the
percentage of the battery’s state of charge using
soft key to view the FULL CHG screen.
The FULL CHG (CHARGE) screen overrides the
%SOC stop function by establishing a time period
from 1-30 days using the
soft keys. When the FLEXnet DC measured days
since a full charge exceeds this 1-30 day user-
determined time, the %SOC stop is ignored and a
full charge takes place. This screen function can be
set to disabled as well (no full charge will occur).
Press the
%SOC START menu.
Press the
AGS/PG3 screen.
ADV/MATE/AGS/%SOC--------------
%SOC start %
DOWN AGS INC DEC
ADV/MATE/AGS/%SOC--------------
%SOC stop 90%
DOWN AGS INC DEC
ADV/MATE/AGS/%SOC--------------
end of %SOC
START menu
UP TOP AGS
ADV/MATE/AGS/FULL CHG
charge to 100% full
disabled
DOWN UP INC DEC
State of Charge