HBX-Drop Grid Set Point
HBX-Drop Grid Delay
ADV/MATE/HBX---------------------
hbx-drop 26.0 vdc
grid setpoint
DOWN UP INC DEC
ADV/MATE/HBX---------------------
hbx-drop 01.0 hrs
grid delay
DOWN UP INC DEC
This set point shows the voltage—26.0 VDC
is the default for a 24V system—at which the
FX will DROP its AC input source. The battery
voltage must remain above this voltage for the
amount of time set by HBX-DROP GRID DELAY
(next screen) for a DROP to be issued. Press the
This set point is the amount of time—01.0 hrs in
this case—battery voltage must remain above the
HBX-DROP GRID SET POINT (see previous
screen) before a DROP command is sent. It can
range from 00.1 hrs to 24.0 hrs in 0.1 hour incre-
ments. These increments are adjusted using the
soft key to proceed.
With this screen, HBX Mode can be enabled or
disabled. Pressing
change the current mode in the next screen.
AC Input Control
ADV/MATE/HBX---------------------
ac input USE
control
DOWN UP CHANGE
NOTE: Before enabling HBX Mode, make sure the
FX is in DROP mode by pressing the
soft key. The screen will indicate DROP mode,
allowing the MATE to reset the HBX values.
ADV/MATE/HBX---------------------
ac input USE
control
DROP USE HBX DONE