HBX-Drop Grid Set Point

HBX-Drop Grid Delay

ADV/MATE/HBX---------------------

hbx-drop 26.0 vdc

grid setpoint
DOWN UP INC DEC

ADV/MATE/HBX---------------------

hbx-drop 01.0 hrs

grid delay
DOWN UP INC DEC

This set point shows the voltage—26.0 VDC

is the default for a 24V system—at which the

FX will DROP its AC input source. The battery

voltage must remain above this voltage for the

amount of time set by HBX-DROP GRID DELAY

(next screen) for a DROP to be issued. Press the

soft key to proceed.

This set point is the amount of time—01.0 hrs in

this case—battery voltage must remain above the

HBX-DROP GRID SET POINT (see previous

screen) before a DROP command is sent. It can

range from 00.1 hrs to 24.0 hrs in 0.1 hour incre-

ments. These increments are adjusted using the

and soft keys. Press the

soft key to proceed.

With this screen, HBX Mode can be enabled or

disabled. Pressing allows you to

change the current mode in the next screen.

AC Input Control

ADV/MATE/HBX---------------------

ac input USE

control
DOWN UP CHANGE

NOTE: Before enabling HBX Mode, make sure the

FX is in DROP mode by pressing the

soft key. The screen will indicate DROP mode,

allowing the MATE to reset the HBX values.