VC Profile Failover fails during Onboard Administrator replacement

If an enclosure has two Onboard Administrators with redundancy and one fails, then the redundant
Onboard Administrator might take several minutes to take over. The VC Profile Failover operation
fails when source or spare bays are associated with an enclosure while the redundant Onboard
Administrator is still in the process of taking over.

To resolve this issue:
1.

Wait until Onboard Administrator has failed over. Perform an Systems Insight Manager
discovery to rediscover the new Onboard Administrator IP address. If the address is not
rediscovered, see the HP BladeSystem c-Class Onboard Administrator User Guide.

2.

If you initiated VC Profile Failover through the VCEM GUI:
a.

From the VCEM home page, click the Profiles tab.

b.

Select the server profile to failover and click Failover. The Virtual Connect
Enterprise Manager is executing the request

message appears.

c.

Click OK to go to the Jobs page and monitor job progress.

VCEM cannot power down ProLiant server model BL465 G1

All VCEM operations that explicitly power down the server (such as VC Profile Failover, Momentary
Press or Press and Hold) might not work well for ProLiant server model BL465c G1 unless the
Onboard Administrator firmware version is 2.25. If you are managing enclosures that contain
ProLiant server model BL465c G1, verify that you use Onboard Administrator firmware version
2.25.

After a VC Domain is removed from a VC Domain Group in VCEM, a
profile with external-managed status cannot be edited through Virtual
Connect Manager

This situation occurs when the profile address is not in the released range selected during the
remove VC Domain from VC Domain Group or delete entire VC Domain Group operations. To
make changes to such server profiles, you must bring the VC Domain under VCEM control and
then update the server profile through the VCEM profile editor.

Server profile edit operation fails when target server is powered on

If you edit a server profile in VCEM and add, remove, or change an Ethernet network connection,
add, remove, or change Fibre Channel SAN connections or change the server profile name, the
edit server profile job might fail with the following message in the job details:

Error during Edit server profile [Profile Name]. Details: This action

could not be performed because the server is powered on. Power down the

server associated with the Server Bay and retry the operation.

VCEM server profile editor allows profile edit operations in case the target server is powered off.
However, the VCEM server profile edit job might fail depending on what profile changes each VC
Domain firmware version allows if the target server is powered on.

VC Domain status is "Mismatch Configuration" after cancel a VC Domain
Maintenance operation fails

This situation occurs when the server profiles from a VC Domain managed by VCEM have changed
and do not match the existing server profiles in the VCEM database. For example, restoring an
old VC Domain backup that has a different server profile from the current VC Domain in the VCEM
database.