NORD Drivesystems BU0290 User Manual
Page 64
PROFINET bus module for NORD frequency inverters SK 200E
64
Subject to technical amendments
BU 0290 GB-4312
7.2.2
Table of possible error messages in the bus module
The following error messages concern bus-related messages, which are indicated on the PROFINET module
SK TU4-PNT(-
…)) All SK TU4-PNT error messages are displayed in parameter (P170) of the bus module and
trigger an error in the connected FI. This is permanently stored in the FI error statistics. The error messages in
the bus module memory (P170) parameter are lost when the 24V supply voltage is switched off.
Error number
Fault
Text in the ParameterBox
Cause
Remedy
Group
Details in
P170
E1000
1000
EEPROM error
Module faulty
1010
System bus 24V missing
Check connections and supply cables
Ensure 24V voltage supply
1020
System bus timeout
Check time set in parameter (P151).
Telegram transfer is faulty.
Check external connection
Check bus protocol program process.
Check bus master.
1030
System bus OFF
Check connections and supply cables
Ensure 24V voltage supply
Check bus master.
5500
No Ethernet
No Ethernet connection
Connect module to Ethernet
5501
Hardware error, IO chip
EMC fault or IO chip defective
Check connections, shielding, cable run
Restart module