2 signal status leds – NORD Drivesystems BU0290 User Manual

Page 21

background image

3 Displays and diagnosis

BU 0290 GB-4312

Subject to technical amendments

21

3.1.2

Signal status LEDs

This manual only describes the LED signal statuses of the PROFINET IO modules. Information for the
frequency inverter LEDs (SK 200E) can be found in the relevant manual (BU0200).
The statuses indicated by the LED can be read out with the aid of a parameterisation tool from Getriebebau
Nord (NORDCON software ParameterBox) and also of course via the information parameter (P173) “Module
Status” (See Section 6.2.3 "BUS module information parameters, general (P17x)").

3.1.2.1 Module-specific displays

The status of the technology unit or the system bus is indicated by the LEDs DS and DE.

DS

(Device State)

Green LED

DE

(Device Error)

Red LED

Meaning

long flashing

= 0.5 s on / 1 s off

short flashing

= 0.25 s on / 1 s off

OFF

OFF

Technology unit not ready, no control voltage

ON

OFF

Technology unit ready, no error, at least one frequency inverter is
communicating via the system bus

ON

Short flashing

Technology unit ready, however
 one or more of the connected frequency inverters has a fault status

(see frequency inverter manual)

Long flashing

OFF

Technology unit ready and at least one further subscriber is connected
to the system bus, but
 No frequency inverter on the system bus (or connection interrupted)
 Address error for one or more system bus participants

Long flashing

Short flashing

Flash interval

1 x - 1s pause

System bus is in status "Bus Warning"
 Communication on system bus interrupted or
 no other participant present on the system bus

Long flashing

Short flashing

Flash interval

2 x - 1s pause

 System bus is in status "Bus off" or
 the system bus 24V power supply was interrupted during operation

Long flashing

Short flashing

Flash interval

3 x - 1s pause

No system bus 24V power supply

(system bus is in status "Bus off")

Long flashing

Short flashing

Flash interval

4 x - 1s pause

 PROFINET error of the technology unit

Details: LED flashing code: RUN and BF
(Section 3.1.2.2 "PROFINET displays"

OFF

Short flashing

Flash interval

1…7 x - 1s pause

System error, internal program sequence interrupted
 EMC interference (observe wiring guidelines!)
 Module faulty

Table 5 LED display, DS and GB