P543, Actual bus value 1 … 3, P546 – NORD Drivesystems BU0290 User Manual
Page 51: Fnct. bus setpoint 1

6 Parameters
BU 0290 GB-4312
Subject to technical amendments
51
Parameters
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P543
… [-01]
...
… [-03]
Actual bus value 1 … 3
(Actual bus value 1 … 3)
SK 2xxE
S
P
0 ... 22
{ [-01] = 01 }
{ [-02] = 04 }
{ [-03] = 09 }
The return value can be selected for bus actuation in this parameter.
NOTE:
For further details, please refer to the description of (P418).
… [-01] = Actual bus value 1
… [-02] = Actual bus value 2
… [-03] = Actual bus value 3
Possible values which can be set:
0 = Off
1 = Actual frequency
2 = Actual speed
3 = Current
4 = Torque current (100% = P112)
5 = State of digital inputs and outputs
2
6 = ... 7 Reserved
8 = Setpoint frequency
9 = Error number
10 = ... 11 Reserved
12 = Bus Out bits 0...7
13 = ... 16 Reserved
17 = Value analog input 1 (P400)
18 = Value analog input 2 (P400)
19 = Setpoint frequency master value (P503)
20 = Setpoint frequency after master value ramp
21 = Actual frequency without master value slip
22 = Speed from encoder
P546
… [-01]
...
… [-03]
Fnct. Bus setpoint 1 ... 3
(Function of bus setpoint 1 ... 3)
SK 2xxE
S
P
0 ... 24
{ [-01] = 01 }
{ [-02] = 00 }
{ [-03] = 00 }
In this parameter, a function is allocated to the output setpoint during bus actuation.
NOTE:
For further details please refer to the description of (P400).
… [-01] = Bus setpoint value 1
… [-02] = Bus setpoint value 2
… [-03] = Bus setpoint value 3
Possible values which can be set:
0 = Off
1 = Setpoint frequency (16 bit)
2 = Frequency addition
3 = Frequency subtraction
4 = Minimum frequency
5 = Maximum frequency
6 = PI process controller actual value
7 = PI process controller setpoint
8 = Actual frequency PID
9 = Actual PID frequency limited
10 = Actual PID frequency monitored
11 = Limiting torque current
12 = Torque current switch-off limit
13 = Limiting current
14 = Current switch-off limit
15 = Ramp time
16 = Lead torque (P214) multiplication
17 = Servo mode torque
18 = Curve travel calculator
19 = Digital In bits 0...7
20 = ...24 reserved for Posicon
2
The assignment of the digital inputs for P543 = 5
Bit 0 = DigIn 1 (FU)
Bit 1 = DigIn 2 (FU)
Bit 2 = DigIn 3 (FU)
Bit 3 = DigIn 4 (FU)
Bit 4 = PTC input (FU)
Bit 5 = Reserved
Bit 6 = DigOut 3 (DO1, 1.SK…IOE)
Bit 7 = DigOut 4 (DO2, 1.SK…IOE)
Bit 8 =
DigIn 5 (DI1, 1.SK…IOE)
Bit 9 = DigIn 6 (DI2, 1.SK…IOE)
Bit 10 = DigIn 7 (DI3, 1.SK…IOE)
Bit 11 = DigIn 8 (DI4, 1.SK…IOE)
Bit 12 = DigOut 1 (FU)
Bit 13 = mech. brake (FU)
Bit 14 = DigOut 2 (FI) (SK 2x0E)