Writing the frequency inverter parameter P105 Index 0 (maximum frequency)
The maximum frequency parameter is to be set to the value 60Hz in data record 1 (Index 0).
Data record 47 is used:
Field
Data size Byte Date
Explanation
Order reference
1 Byte
1
xx h The order reference is used for the precise allocation of the SK
TU4-PNT response
Order label
1 Byte
2
02 h Write parameter value (refer to Section 5.2.3.1)
Axis
1 Byte
3
01 h
Access to FI parameter (0=TU4, 1=FU1, … 4=FU4)
Parameter number
2 Bytes
4
5
04 h
51 h
Parameter number P105 (+1000) = 451 h
Parameter index
2 Bytes
6
7
00 h
00 h
Parameter sub-index (refer to Section 5.2.3.2)
Parameter value
4 Bytes
8
9
10
11
00 h
00 h
02 h
58 h
The maximum frequency 60Hz (600 = 258 h) is to be set
Table 30 Example telegram for writing parameter P105[-01]
S7 Code example:
CALL "WRREC" , DB53
WriteRequest
REQ :=#bStart
ID :=DW#16#7FC
Diagnosis address
INDEX :=47
Data record 47
LEN :=11
Length: 11 Bytes
DONE :=#bEnde
BUSY :=#bBusy
ERROR :=#bError
STATUS:=#wStatus
RECORD:=P#DB10.DBX0.0 BYTE 8
Data: xxh, 02h, 01h, 04h,51h, 00h, 00h, 00h, 00h, 02h, 58h
CALL "RDREC" , DB52
ReadResponse
REQ :=#bStart
ID :=DW#16#7FC
Diagnosis address
INDEX :=47
Data record 47
MLEN :=11
VALID := …
BUSY := …
ERROR := …
STATUS:= …
LEN := …
RECORD:=P#DB10.DBX12.0 BYTE 8
Response: xxh, 02h, 01h, 04h,51h, 00h,00h, 00h,00h, 00h, 00h