P173 module status, P174 status of digital input, P175 relay status – NORD Drivesystems BU0290 User Manual
Page 58
PROFINET bus module for NORD frequency inverters SK 200E
58
Subject to technical amendments
BU 0290 GB-4312
Parameters
Setting value / Description / Note
Device
Parameter
type
P173
Module status
(Module status)
SK TU4-PNT
16 bit
0 ... FFFF (hex)
Explanation of bits:
Bit 0 = Initialisation
Bit 1 = AR installed
Bit 2 = Reserved
Bit 3 = Timeout (P151 / P513)
Bit 4 = Reserved
Bit 5 = Ethernet connection
Bit 6 = System bus “BUS WARNING”
Bit 7 = System bus "BUS OFF"
Bit 8 = Status FI 1
Bit 9 = Status FI 1
Bit 10= Status FI 2
Bit 11= Status FI 2
Bit 12= Status FI 3
Bit 13= Status FI 3
Bit 14= Status FI 4
Bit 15= Status FI 4
Status for FI x:
Bit High
Bit Low status
0
0
FI is offline
0
1
unknown FI
1
0
FI is online
1
1
FI missing or switched off
P174
Status of digital input
(Status of digital inputs)
SK TU4-PNT
8 bit
0 ... 255
dec
(00000000 ... 11111111)
bin
Instantaneous view of input level logic.
Possible displayed values:
Bit 0= Input 1 ((DIN1) (of BUS module))
Bit 1= Input 2 ((DIN2) (of BUS module))
Bit 2= Input 3 ((DIN3) (of BUS module))
Bit 3= Input 4 ((DIN4) (of BUS module))
Bit 4= Input 5 ((DIN5) (of BUS module))
Bit 5= Input 6 ((DIN6) (of BUS module))
Bit 6= Input 7 ((DIN7) (of BUS module))
Bit 7= Input 8 ((DIN8) (of BUS module))
P175
Relay status
(Status of relays / Digital outputs)
SK TU4-PNT
8 bit
0 ... 3
dec
(00 ... 11)
bin
Instantaneous view of output level logic.
Possible displayed values:
Bit 0= Output 1 ((DO1) (of BUS module))
Bit 1= Output 2 ((DO2) (of BUS module))