5 communication, 1 process data, 1 process data structure – NORD Drivesystems BU0290 User Manual
Page 29: 5 communication 5.1 process data, Process data structure
5 PROFINET - Data transfer
BU 0290 GB-4312
Subject to technical amendments
29
5 Communication
5.1 Process data
Control words and setpoints are transferred from the bus master / controller to the SK TU4-
…bus module as
process data and in return, the status word and actual values are sent to the bus master / controller from the
FI. Transfer is carried out cyclically. The bus master / controller can access these process values directly, as
they are stored in the IO area.
The length and structure of the process data is specified via the PPO types during the planning of the
PROFINET network.
The allocation of the values transferred in the setpoint/actual value area of the FI is made via the parameters
P543 to P548 or P543 [-
01]…[-05] and P546 [-01] …[-05]..
5.1.1
Process data structure
The structure of the process data is defined by the PPO type.
5.1.1.1
Pure process data communication
Direction of
transmission
Transmitted data
( 4 Byte )
1st word
2nd word
... to SK TU4
Control word
Setpoint 1
... from the SK TU4
Status word
Actual
value 1
Table 11: PPO 3
Direction of
transmission
Transmitted data
( 8 Byte )
1st word
2nd word 3rd word
4th word
... to SK TU4
Control word
Setpoint
1
Setpoint
2
Setpoint
3
... from the SK TU4
Status word
Actual
value 1
Actual
value 2
Actual
value 3
Table 12: PPO 4
Direction of
transmission
Transmitted data
( 12 Byte )
1st word
2nd word 3rd word
4th word
5th word
6th word
... to SK TU4
Control word
Setpoint
1
Setpoint
2
Setpoint
3
Setpoint
4
Setpoint
5
... from the SK TU4
Status word
Actual
value 1
Actual
value 2
Actual
value 3
Actual
value 4
Actual
value 5
Table 13: PPO 6