PROFINET bus module for NORD frequency inverters SK 200E

18

Subject to technical amendments

BU 0290 GB-4312

Terminal/
Designation

Function

Data

Description /
wiring suggestion

Parameter

25

DIN2

Digital input 2

(I/O PROFINET DIN2)

Low 0V ... 5V
High 15V ... 30V
R

i

= 8.1k

Input capacitance 10nF
Scan rate 1 ms
Inputs as per
EN 61131-2

Type 1

Each digital input has a
reaction time of 3 ms.

P174

26

DIN4

Digital input 4

(I/O PROFINET DIN4)

P174

27

0V


28

GND
Reference potential
for digital signals

As for terminal 15

Connection of supply voltage
for module and 24V source for
supply of the digital inputs
(DIN1 to DIN8)

-

29

24V


30

24V supply

(Module and system bus
level)

As for terminal 1
However, max. permissible
current load: 3A

-

Potential isolation

31

24V2

24V supply
of digital outputs

24VDC -/+20%
Up to 1A, according to load
reverse polarity protected

Supply voltage connection for
digital outputs (DO1 and DO2)
If necessary, bridge to

24V

terminal

-

32

0V2

GND 2
Reference potential
for digital outputs

Ground for digital outputs (DO1
and DO2)

If necessary, bridge to

0V

terminal

-

33

DO1

Digital output 1

(I/O PROFINET DO1)

Low = 0V
High: 24V
Rated current: 500mA each

The digital outputs should be
used with a separate 24V
supply

P150
P175

34

DO2

Digital output 2

(I/O PROFINET DO2)

P150
P175

35

0V2


36

GND 2
Reference potential
for digital outputs

Ground for digital outputs (DO1
and DO2)

If necessary, bridge to

0V

terminal

-

Table 4 Connection assignment of BUS connection unit for PROFINET IO