7 Error monitoring and error messages

BU 0290 GB-4312

Subject to technical amendments

63

7.2 Error messages

7.2.1

Table of possible error messages (caused by the bus) in the frequency inverter

The following error messages concern bus-related messages which are indicated on the frequency inverter.
A complete list of error messages for the frequency inverter (SK 200E) can be found in the relevant manual
(BU0200).

Error number
Display in the
SimpleBox

Fault

Text in the ParameterBox

Cause

Remedy

Group

Details in
P700 / P701

E010

10.0

Connection error

Contact to SK TU4-PNT interrupted. (SK 500E)

10.3

Timeout via (P151)

Telegram transfer is faulty.

Check watchdog time (P151)

Check physical bus connections

Contains cyclic telegrams

10.4

Hardware error, IOs

An error has occurred at the IO interfaces

Check connections (short circuit)

Restart the module

10.5

General PROFINET
configuration error

A general configuration error has occurred.

No Ethernet connection.

10.8

Timeout - connection error

The connection between the FI and the SK TU4-PNT had a
timeout

10.9

Module missing / P120

The module entered in parameter (P120) is not available.