7 timeout monitoring – NORD Drivesystems BU0290 User Manual
Page 36
PROFINET bus module for NORD frequency inverters SK 200E
36
Subject to technical amendments
BU 0290 GB-4312
5.1.6
Example for switching the frequency inverter on and off
In this example, a frequency inverter will be operated with a setpoint (setpoint frequency) and an actual value
(actual frequency). The "Maximum Frequency" is 50Hz.
Parameter settings:
P105 = 500
P543 = 1
P546 = 1
Control
word
Setpoint 1
Status
word
Actual
value 1
Explanation
- - -
- - -
0000h
0000h
- - -
- - -
xx40h
0000h
The mains voltage is switched on at the FI
047Eh
0000h
xx31h
0000h
FI is set to "Standby" status
047Fh
2000h
xx37h
2000h
FI is set to "Operation enabled" status and controlled with a
50% setpoint.
The FI is enabled, the motor is supplied with current and rotates with a frequency of 25Hz.
0047Eh
2000h
xx31h
0000h
FI is set to "Standby" status, the motor runs up its
parameterised ramp to speed 0 and is switched off.
The FI is disabled again and the motor is without current.
047Fh
1000h
xx37h
1000h
FI is set to "Operation enabled" status and controlled with a
25% setpoint.
The FI is enabled, the motor is supplied with current and rotates with a frequency of 12.5Hz.
Table 20 Example of setpoint specification
5.1.7
Timeout monitoring
The PROFINET IO data traffic can be monitored with a watchdog with the aid of the time set in parameter
P151. If no further cyclical data is sent from the PROFINET IO controller, a module error is detected and set in
the FI (E10.3).
Monitoring via the FI parameter P513 is also possible. This is triggered if the process data contact is
interrupted or the process data is transferred with an invalid control word (Bit10 in control word = 0). This
function is activated when the first valid process data telegram is received.