beautypg.com

NORD Drivesystems BU0290 User Manual

Page 40

background image

PROFINET bus module for NORD frequency inverters SK 200E

40

Subject to technical amendments

BU 0290 GB-4312

AK

Function

0

No response

1

Transfer parameter value (word)

2

Transfer parameter value (double word)

4

Transfer parameter value (array word)

5

Transfer parameter value (array double word)

7

Order cannot be executed (with error number in PWE2)

Table 25 Response labels - Meaning


In the response label "Order cannot be executed" (AK = 7), then an error message is added to the parameter
value (PWE2) of the inverter response. For the meanings of the values transferred, please refer to the
following table.

No.

Meaning

0

Invalid parameter number

1

Parameter value cannot be changed

2

Lower or upper value limit exceeded

3

Incorrect sub-index

4

No array

5

Invalid data type (at present only for SK 700E)

6

Only resettable (only 0 may be written)

7

Description element cannot be changed

9

Description data not present

201

Invalid order element in the last order received

202

Internal response label cannot be depicted

Table 26 Response labels

– Explanation of error numbers for response label = 7

NOTE

Both the order label and the response label are abbreviated as AK. Therefore, care must be
taken when reading or interpreting the order processing description in this section.