BU 0290 GB-4312
6 Parameters
In order to enable communication via PROFINET IO, the frequency inverter and the PROFINET IO technology
unit must be parameterised accordingly.
6.1 Parameters for frequency inverter SK200E
The following list of parameters for the frequency inverter series SK 200E are directly relevant for the operation
of the frequency inverter via PROFINET IO. A complete list of parameters for the frequency inverter (SK 200E)
can be found in the relevant manual (BU0200).
6.1.1
Basic parameters (P1xx)
Parameters
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P120
… [-01]
...
… [-04]
Option monitoring
(Options monitoring)
SK 2xxE
S
0 ... 2
{ 1 }
Array levels:
Setting value for each array:
… [-01] = Extension 1 (BUS TB)
… [-02] = Extension 2 (2 .I/O-TB)
(ZBG2)
… [-03] = Extension 3 (1st. I/O TB)
(ZBG1)
… [-04] = Extension 4 (reserved)
0 = Monitoring OFF
1 = Auto, communication is only monitored if
an existing communication is interrupted.
If a module which was previously present
is not found when the network is switched
on, this does not result in an error.
Monitoring only becomes active when the
extension begins communication with the
FI.
2 = Monitoring active immediately; the FI
starts monitoring the corresponding
module immediately after it is switched
on. If the module is not detected on
switch-on, the FI remains in the status
"not ready for switch-on" for
5 seconds and then triggers an error
message.