6 Parameters

In order to enable communication via PROFINET IO, the frequency inverter and the PROFINET IO technology
unit must be parameterised accordingly.

6.1 Parameters for frequency inverter SK200E

The following list of parameters for the frequency inverter series SK 200E are directly relevant for the operation
of the frequency inverter via PROFINET IO. A complete list of parameters for the frequency inverter (SK 200E)
can be found in the relevant manual (BU0200).

6.1.1

Basic parameters (P1xx)

Parameters

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter

set

P120

… [-01]

...

… [-04]

Option monitoring

(Options monitoring)

SK 2xxE

S

0 ... 2

{ 1 }

Array levels:

Setting value for each array:

… [-01] = Extension 1 (BUS TB)
… [-02] = Extension 2 (2 .I/O-TB)

(ZBG2)

… [-03] = Extension 3 (1st. I/O TB)

(ZBG1)

… [-04] = Extension 4 (reserved)

0 = Monitoring OFF
1 = Auto
, communication is only monitored if

an existing communication is interrupted.
If a module which was previously present
is not found when the network is switched
on, this does not result in an error.
Monitoring only becomes active when the
extension begins communication with the

FI.

2 = Monitoring active immediately; the FI

starts monitoring the corresponding
module immediately after it is switched

on. If the module is not detected on
switch-on, the FI remains in the status

"not ready for switch-on" for
5 seconds and then triggers an error

message.