PROFINET bus module for NORD frequency inverters SK 200E

48

Subject to technical amendments

BU 0290 GB-4312

Parameters

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter

set

P481

... [-01]

...

... [-10]

Function of BusIO Out Bits

(Function Bus I/O Out Bits)

SK 2xxE

0 ... 39

{ [-01] = 18 }

{ [-02] = 08 }

{ [-03] = 30 }

{ [-04] = 31 }

{ [-05...-10] = 00 }

The bus I/O Out bits are perceived as multi-function relay outputs. They can be set to the same
functions (P434).

These I/O bits can also be used in combination with the AS Interface (SK 225E or SK 235E) or
the I/O extension (SK CU4-IOE or SK TU4-IOE).

… [-01] = Bus I/O Out Bit 0
… [-02] = Bus I/O Out Bit 1
… [-03] = Bus I/O Out Bit 2
… [-04] = Bus I/O Out Bit 3
… [-05] = Bus I/O Out Bit 4
… [-06] = Bus I/O Out Bit 5

… [-07] =Flag 1
… [-08] = Flag 2
… [-09] = Bit 10 BUS status word
… [-10] = Bit 13 BUS status word

The possible functions for the bus Out bits can be found in the table of functions for the relay
(P434)

P482

... [-01]

...

... [-10]

Norm. BusIO Out Bits

(Standardisation of bus I/O Out bits)

SK 2xxE

-

400 … 400 %

{ all 100 }

Adjustment of the limit values of the bus Out bits. For a negative value, the output function will
be output negative.

Once the limit value is reached and positive values are delivered, the output produces a High
signal, for negative setting values a Low signal.

P483

... [-01]

...

... [-10]

Hyst. BusIO Out Bits

(Hysteresis of bus I/O Out bits)

SK 2xxE

S

1 … 100 %
{ all 10 }

Difference between switch-on and switch-off point to prevent oscillation of the output signal.