PROFINET bus module for NORD frequency inverters SK 200E
48
Subject to technical amendments
BU 0290 GB-4312
Parameters
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P481
... [-01]
...
... [-10]
Function of BusIO Out Bits
(Function Bus I/O Out Bits)
SK 2xxE
0 ... 39
{ [-01] = 18 }
{ [-02] = 08 }
{ [-03] = 30 }
{ [-04] = 31 }
{ [-05...-10] = 00 }
The bus I/O Out bits are perceived as multi-function relay outputs. They can be set to the same
functions (P434).
These I/O bits can also be used in combination with the AS Interface (SK 225E or SK 235E) or
the I/O extension (SK CU4-IOE or SK TU4-IOE).
… [-01] = Bus I/O Out Bit 0
… [-02] = Bus I/O Out Bit 1
… [-03] = Bus I/O Out Bit 2
… [-04] = Bus I/O Out Bit 3
… [-05] = Bus I/O Out Bit 4
… [-06] = Bus I/O Out Bit 5
… [-07] =Flag 1
… [-08] = Flag 2
… [-09] = Bit 10 BUS status word
… [-10] = Bit 13 BUS status word
The possible functions for the bus Out bits can be found in the table of functions for the relay
(P434)
P482
... [-01]
...
... [-10]
Norm. BusIO Out Bits
(Standardisation of bus I/O Out bits)
SK 2xxE
-
400 … 400 %
{ all 100 }
Adjustment of the limit values of the bus Out bits. For a negative value, the output function will
be output negative.
Once the limit value is reached and positive values are delivered, the output produces a High
signal, for negative setting values a Low signal.
P483
... [-01]
...
... [-10]
Hyst. BusIO Out Bits
(Hysteresis of bus I/O Out bits)
SK 2xxE
S
1 … 100 %
{ all 10 }
Difference between switch-on and switch-off point to prevent oscillation of the output signal.