Example telegrams – NORD Drivesystems BU0260 User Manual
Page 93
7 CANopen Data transfer
BU 0260 GB
Subject to technical amendments
93
7.4.2
Example telegrams
Various example telegrams are shown below to clarify the control and parameterisation of the frequency
inverter with the various field bus systems.
7.4.2.1 Example for switching the frequency inverter on and off
In this example, a FI will be operated with a setpoint (setpoint frequency) and an actual value (actual
frequency). The "maximum frequency" is 50Hz.
Parameter settings:
P105 = 50
P543 = 1
P546 = 1
Control
word
Setpoint 1
Status
word
Actual
value 1
Explanation
- - -
- - -
0000
hex
0000
hex
- - -
- - -
xx40
hex
0000
hex
The mains voltage is switched on at the FI
047E
hex
0000
hex
xx31
hex
0000
hex
FI is set to "Standby" status
047F
hex
2000
hex
xx37
hex
2000
hex
FI is set to "Operation enabled" status and controlled with a
50% setpoint.
The FI is enabled, the motor is supplied with current and rotates with a frequency of 25Hz.
0047E
hex
2000
hex
xx31
hex
0000
hex
FI is set to "Standby" staus, the motor runs up its
parameterised ramp to speed 0 and is switched off.
The FI is disabled again and the motor is without current.
047F
hex
1000
hex
xx37
hex
1000
hex
FI is set to "Operation enabled" status and controlled with a
25% setpoint.
The FI is enabled, the motor is supplied with current and rotates with a frequency of 12.5Hz.
7.4.2.2 CANopen with USS process data
The following example is designed to clarify control using PDOs. The following settings are assumed:
FI 1 on field bus module SK xU4-CAO
Node-ID
"4"
Parameter (P509) "Source control word"
for SK500E: Setting: {6} "CANopen control word" (object number (21FD
hex
) = 6) or
for SK200E: Setting: {3} "System bus" (object number (21FD
hex
) = 3,
(P510)= {0}
Rx-PDO1 is used for control. The device transmits its actual values via Tx-PDO1
The drive profile is disabled
for SK 500E: Setting: (P551) = {0} or
for SK200E: Setting: (P168 [-01]) = {0}
Identifier
Rx-PDO1: 0200
hex
+ NODE-ID
0204
hex
Tx-PDO1: 0180
hex
+ NODE-ID
0184
hex