NORD Drivesystems BU0260 User Manual
Page 80
Supplementary Manual CANopen for NORDAC SK 20E
80
Subject to technical amendments
BU 0260 GB
6.2.2
Table of possible error messages in the bus module
The following error messages concern bus-related messages, which are indicated on the CANopen module
(SK CU4-CAO or SK TU4-CAO(-…)).
Error number
Fault
Text in the ParameterBox
Cause
Remedy
Group
Details in
P170
E1000
1000 EEPROM
error
Module faulty
1010
System bus 24V missing
Check connections and supply cables
Ensure 24V voltage supply
1020
System bus timeout
Check time set in parameter (P151).
Telegram transfer is faulty.
Check external connection.
Check bus protocol program process.
Check bus master.
1030
System bus OFF
Check connections and supply cables
Ensure 24V voltage supply
Check bus master.
5110
CANopen bus OFF
Subscriber is disconnected from bus
5111 CANopen
warning
Bus error
No other subscriber present on the system bus
Wiring not correct (cable length, spur cables)
No valid ID (DIP switch)
5112 CANopen
overrun
Message box (message buffer) for the module was
overwritten by a new telegram before processing
Increase master inhibit time
Reduce baud rate
5113
Invalid CANopen address
Avoid double assignment of addresses
Comply with address range 1 ... 63
5120 CANopen
timeout
Telegram transfer is faulty.
Check external connection.
Check bus protocol program process.
Check bus master.