NORD Drivesystems BU0260 User Manual
Page 84
Supplementary Manual CANopen for NORDAC SK 20E
84
Subject to technical amendments
BU 0260 GB
7.2.1.1 Control word (STW)
In the order telegram, in the area of the process data the control word (STW) is transferred to the frequency
inverter as the first word (taking into account the "Little Endian" format). For example, a control word "ready for
switch-on" corresponds to 047E
(hex)
, whereby in Byte 0 the value 7E
(hex)
and in Byte 1 the value 04
(hex)
are
transferred.
PZD1 PZD2 PZD3 PZD4
STW SW1 SW2/3
SW2/3
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Meaning of the individual bits:
Bit
Value Significance
Comments
0
0
OFF 1
Return with the brake ramp, at f=0Hz voltage activation
1 ON
Standby
1 0 OFF
2
Disable voltage; the inverter output voltage is switched off, the FI goes into
switch-on disabled status.
1 Operating
condition
OFF 2 is cancelled
2 0 OFF
3
Emergency stop with programmed emergency stop time; at f = 0Hz voltage
enable; the FI goes into switch-on disabled status
1 Operating
condition
OFF 3 is cancelled
3 0 Disable
operation Disable voltage; the inverter output voltage is switched off, the FI goes into
standby status.
1
Enable operation
Output voltage enabled, run-up to present setpoint.
4 0 Disable run-up
encoder
Run-up encoder is set to zero; at f = 0Hz no voltage enable; FI remains in
operation enabled status.
1
Operating condition
Run-up encoder is enabled
5
0
Stop run-up encoder
Freezing of actual setpoint from run-up encoder (hold frequency).
1
Enable run-up encoder Enable setpoint on run-up encoder
6
0
Disable setpoint
Selected setpoint is set to zero in the run-up encoder.
1
Enable setpoint
Selected setpoint on run-up encoder is activated.
7
0
No acknowledgement
With the switch from 0 to 1, errors which are no longer active are acknowledged.
1 Acknowledge
Note: If a digital input is programmed to the function "Error ack.", this bit must not
be set permanently to 1 via the bus (otherwise this will prevent edge detection).
8 0
1
Bit 8 active
Bus bit 8 from the control word is set. (Only for SK 200E and SK 500E)
For further details of the function please refer to parameter (P480).
9 0
1
Bit 9 active
Bus bit 9 from the control word is set. (Only for SK 200E and SK 500E)
For further details of the function please refer to parameter (P480).
10
0
PZD invalid
The transmitted process data is invalid.
1
PZD valid
Valid process data is transferred from the master.
Note:If setpoints only are transferred via the bus, this bit must be set so that the
transferred setpoint is valid.
11 0
1 Rotation
right
Rotation right (priority) is on.
12 0
1 Rotation
left
Rotation left is on.
13 0/1
Reserved
14 0/1 Parameter set switch
Bit 0
00 = Parameter set 1
01 = Parameter set 2
10 = Parameter set 3
11 = Parameter set 4
15 0/1 Parameter set switch
Bit 1