2 error messages 6.2.1 – NORD Drivesystems BU0260 User Manual
Page 79
6 Error monitoring and error messages
BU 0260 GB
Subject to technical amendments
79
6.2 Error messages
6.2.1
Table of possible error messages (caused by the bus) in the frequency inverter
The following error messages concern bus-related messages which are indicated on the frequency inverter.
A complete list of error messages for the frequency inverter (SK 200E) can be found in the relevant manual
(BU0200).
Error code
display on the
SimpleBox
Fault
Text in the ParameterBox
Cause
Remedy
Group
Details in
P700 / P701
E010
10.2
External bus module
telegram timeout
Telegram transfer is faulty.
Check external connection.
Check bus protocol program process.
Check bus master.
10.3
Timeout via (P151)
Telegram transfer is faulty.
Check watchdog time (P151)
Check physical bus connections
Contains cyclic telegrams
10.4
External bus module
initialisation failure
Bus module cannot be accessed
Check bus module power supply
10.8 External
module
communication failure
Connection fault / error in the external module to the FI
10.9
Module not found
The module entered in parameter (P120) is not available.