NORD Drivesystems BU0260 User Manual
Page 72
Supplementary Manual CANopen for NORDAC SK 20E
72
Subject to technical amendments
BU 0260 GB
5.2.3
BUS module information parameters, general (P170)
Parameter
Setting value / Description / Note
Device
Supervisor
Parameter
set
P170
...
[-01]
...
[-02]
Current error
0 ... 9999
Current error present. Further details in Section 6.2 "Error messages".
… [-01 ] = Current module error
… [-02 ] = Last module error
Possible values:
1000 = EEPROM error
1010 = System bus 24V missing
1020 = System bus timeout (see time in P151)
1030 = System bus OFF
Specific to CANopen
5110 = CANopen bus OFF
5111 = CANopen warning
5112 = CANopen overrun
5113 = CANopen invalid address
5120 = CANopen timeout / communication error
P171
... [-01]
...
...
[-03]
Software version/ Revision
0,0 ... 9999.9
This parameter shows the software and revision numbers in the module. Array 03 provides
information about any special versions of the hardware or software A zero stands for the
standard version.
… [-01] = Software version
… [-02] = Software revision
… [-03] = Special version
P172 Configuration
0 ... 2
The version can be queried in this parameter.
Possible values:
0 = Internal module
1 = External module
2 = Bus TO via SPI