NORD Drivesystems BU0260 User Manual
Page 92
Supplementary Manual CANopen for NORDAC SK 20E
92
Subject to technical amendments
BU 0260 GB
Relevant
bus system
Serial
No.
Step
Comments
F
ield b
us
(CANop
en)
6
Configure bus module
for field bus
24V supply of the field bus level necessary
(see Section 2.2.3 "Configuration")
If the bus module is the last physical subscriber in the field
bus system:
Set termination resistor:
DIP switch "Bus termination CANopen" to "ON"
Set baud rate
Set node address (identifier)
7
Field bus
communcation
Make bus module settings:
(P168 [-01]):
{ 0 } "Profile OFF"
(P162 [-01,-03,-05,-09])
{ 255 }
(P162 [-02,-04,-06,-10])
{ 255 }
(P163)
{ 10 }
(P164)
{ 250 }
(P165), (P160), (P161)
leave at factory setting
System bus
8
Monitoring at system
bus level
(P151):
{ 200 }
(P120 [-01])
{ 1 } or { 2 }
Field bus
(CANopen)
9
Monitoring at field bus
level (node monitoring)
(P166 [-01]):
{ 250 }
(P166 [-02]):
{ 400 }
(P167):
{ 3 }
System bus
10
Checking system bus
communication
(P748):
"System bus status"
(P740 [-01]):
"Control word"
(P740 [-02]):
"Setpoint 1"
(P741 [-01]):
"Status word"
(P741 [-02]):
"Actual value 1"
(P173):
"Module status"
Field bus
(CANopen)
11
Checking field bus
communication
(P173):
"Module status"
(P176):
"PZD Bus In"
(P177):
"PZD Bus Out"
Note: Settings specific to the application (motor data, control parameters, control terminal functions etc.)
cannot of course be described here.