4 Commissioning
BU 0260 GB
Subject to technical amendments
55
4.9.4
Frequency inverter objects (2000
hex
- 3005
hex
)
Index
Sub
Object
Description
Unit
Acc
Type
0x2000-
0x23E7
-
FI parameter
FI parameter
(see parameter (P165)):
0x3000 0 Largest
Subindex
Number of control word elements
RO
U8
0x3000
1
Control word
Control word (STW) FI 1
RW
U16
0x3000
2
Control word
Control word (STW) FI 2
RW
U16
0x3000
3
Control word
Control word (STW) FI 3
RW
U16
0x3000
4
Control word
Control word (STW) FI 4
RW
U16
0x3001 0 Largest
Subindex
Number of status word elements
RO
U8
0x3001
1
Status word
Status word (ZSW) FI 1
RO
U16
0x3001
2
Status word
Status word (ZSW) FI 2
RO
U16
0x3001
3
Status word
Status word (ZSW) FI 3
RO
U16
0x3001
4
Status word
Status word (ZSW) FI 4
RO
U16
0x3002 0 Largest
Subindex
Number of setpoint elements
RO
U8
0x3002
1
Setpoint 1
Setpoint 1 (SW1) FI 1
RW
U16
0x3002
2
Setpoint 2
Setpoint 2 (SW2) FI 1
RW
U16
0x3002
3
Setpoint 3
Setpoint 3 (SW3) FI 1
RW
U16
0x3002
4
Setpoint 1
Setpoint 1 (SW1) FI 2
RW
U16
0x3002
5
Setpoint 2
Setpoint 2 (SW2) FI 2
RW
U16
0x3002
6
Setpoint 3
Setpoint 3 (SW3) FI 2
RW
U16
0x3002
7
Setpoint 1
Setpoint 1 (SW1) FI 3
RW
U16
0x3002
8
Setpoint 2
Setpoint 2 (SW2) FI 3
RW
U16
0x3002
9
Setpoint 3
Setpoint 3 (SW3) FI 3
RW
U16
0x3002
10
Setpoint 1
Setpoint 1 (SW1) FI 4
RW
U16
0x3002
11
Setpoint 2
Setpoint 2 (SW2) FI 4
RW
U16
0x3002
12
Setpoint 3
Setpoint 3 (SW3) FI 4
RW
U16
0x3003 0 Largest
Subindex
Number of actual value elements
RO
U8
0x3003
1
Actual Value 1
Actual value 1 (IW1) FI 1
RO
U16
0x3003
2
Actual Value 2
Actual value 2 (IW2) FI 1
RO
U16
0x3003
3
Actual Value 3
Actual value 3 (IW3) FI 1
RO
U16
0x3003
4
Actual Value 1
Actual value 1 (IW1) FI 2
RO
U16
0x3003
5
Actual Value 2
Actual value 2 (IW2) FI 2
RO
U16
0x3003
6
Actual Value 3
Actual value 3 (IW3) FI 2
RO
U16
0x3003
7
Actual Value 1
Actual value 1 (IW1) FI 3
RO
U16
0x3003
8
Actual Value 2
Actual value 2 (IW2) FI 3
RO
U16
0x3003
9
Actual Value 3
Actual value 3 (IW3) FI 3
RO
U16
0x3003
10
Actual Value 1
Actual value 1 (IW1) FI 4
RO
U16
0x3003
11
Actual Value 2
Actual value 2 (IW2) FI 4
RO
U16
0x3003
12
Actual Value 3
Actual value 3 (IW3) FI 4
RO
U16
0x3004
0
Digital outputs
Control of digital outputs
RW
U16
0x3005 0 Digital
inputs
Status
of digital inputs
RO
U16