4.5.2.6 PDO transmission / access in USS Protocol Mode
The internal status machine of the frequency inverter (USS) applies for the transfer of process data. Access to
the individual frequency inverters is according to the following pattern (see Section 4.9.4 "Frequency inverter
objects (2000hex - 3005hex )").
In the following example of a VIPA control, the linking of the objects (control word and setpoint) of FI 1 to those
of the CANopen master is illustrated.
4th frequency inverter
Setpoint
- PDO in USS Protocol Mode
Sequence in CAN telegram
Indication in word
Index
Sub-index Description
0 0x3000
4
Control
word
(STW)
1
0x3002 10
Setpoint 1 (SW1)
2
0x3002 11
Setpoint 2 (SW2)
3
0x3002 12
Setpoint 3 (SW3)
3rd frequency inverter
Setpoint
- PDO in USS Protocol Mode
Sequence in CAN telegram
Indication in word
Index
Sub-index Description
0 0x3000
3
Control
word
(STW)
1
0x3002 7
Setpoint 1 (SW1)
2
0x3002 8
Setpoint 2 (SW2)
3
0x3002 9
Setpoint 3 (SW3)
2nd frequency inverter
Setpoint
- PDO in USS Protocol Mode
Sequence in CAN telegram
Indication in word
Index
Sub-index Description
0 0x3000
2
Control
word
(STW)
1
0x3002 4
Setpoint 1 (SW1)
2
0x3002 5
Setpoint 2 (SW2)
3
0x3002 6
Setpoint 3 (SW3)
1st frequency inverter
Setpoint
- PDO in USS Protocol Mode
Sequence in CAN telegram
Indication in word
Index
Sub-index Description
0 0x3000
1
Control
word
(STW)
1
0x3002 1
Setpoint 1 (SW1)
2
0x3002 2
Setpoint 2 (SW2)
3
0x3002 3
Setpoint 3 (SW3)
PDO setpoint
Gateway
mode