Supplementary Manual CANopen for NORDAC SK 20E

28

Subject to technical amendments

BU 0260 GB

Baud rate
The baud rate is set in binary code via two DIP
switches (only applies to field bus level).

Setting Baud rate

DIP2 DIP1

1

125 kBaud OFF

OFF

2 250

kBaud

OFF

ON

3 500

kBaud

ON

OFF

4 1

MBaud

ON

ON




Configuration example
A CANopen subscriber SK TU4-CAO is connected to an SK 200E series frequency inverter via a BUS
connection unit SK T14-TU-BUS. The field bus address (CANopen address / identifier) is to be "14". The
CANopen subscriber is not a final subscriber. The system bus only includes the frequency inverter and the
CANopen module. The termination resistor for the system bus is to be set at the frequency inverter. The DIP
switches on the CANopen module must be set as follows:

Area

Significance

DIP switch

No.

DIP Switch

ON - OFF

Configuration

example

Address

ing

Identifier-bit 5

DIP switch

No. 647

8

2

5

0

Identifier-bit 4

7

2

4

0

Identifier-bit 3

6

2

3

8

Identifier-bit 2

5

2

2

4

Identifier-bit 1

4

2

1

2

Identifier-bit 0

3

2

0

0

Example address =

14

Baud

rate

Baud rate-bit 1

2

2

1

0

Baud rate-bit 0

1

2

0

0

Baud rate =

125kBaud

BUS

termination

No significance

DIP switch

No. 802

3

-

-

CANopen

2

OFF

System bus

1

ON


 
 
 
 
 
 
 
 
 

 

E.g.: SK CU4‐CAO 

CANopen baud rate