NORD Drivesystems BU0260 User Manual
Page 56
Supplementary Manual CANopen for NORDAC SK 20E
56
Subject to technical amendments
BU 0260 GB
4.9.5
Error codes – cancellation of parameter communication
The following table gives an overview of the possible error codes which may be generated on cancellation of
parameter communication.
Error code
Description
0x0503 0000
Toggle bit unchanged
0x0504 0000
SDO timeout message
0x0504 0001
Client/Server command invalid / unknown
0x0504 0005
No memory
0x0601 0000
Illegal access to an object
0x0601 0001
Access to write-only parameter
0x0601 0002
Access to read-only object
0x0602 0000
Object does not exist in object dictionary
0x0604 0041
Object cannot be mapped in PDO
0x0604 0042
Object exceeds PDO length
0x0604 0043
Parameter incompatibility
0x0604 0047
Module internally incompatible
0x0606 0000
Access failure due to hardware error
0x0607 0010
Data type or parameter length do not match
0x0607 0012
Data type incorrect, parameter length too long
0x0607 0013
Data type incorrect, parameter length too short
0x0609 0011
Sub-Index of parameter does not exist
0x0609 0030
Parameter value range overflow
0x0609 0031
Parameter value range overflow
0x0609 0032
Parameter value range undershot
0x0800 0020
Data transfer or storage not possible
0x0800 0021
Data transfer or storage not possible; reason: local control
4.9.6
Error messages (EMCY message)
The following error groups are defined in the communication profile DS-301.
Error Code (hex)
Significance
00xx No
error
10xx
Undefined error type
20xx Current
error
30xx Voltage
error
40xx Temperature
error
50xx Hardware
error
60xx Software
error
70xx Additional
module
80xx Communication
90xx External
error
FF00
Specific to device