NORD Drivesystems BU0260 User Manual
Page 10
Supplementary Manual CANopen for NORDAC SK 20E
10
Subject to technical amendments
BU 0260 GB
1.1 Overview
Features of the CANopen Modules
Electrically isolated bus interface
Data transfer rate from 10kbit/sec to 1 Mbit/sec
Easy connection, optionally via M12 round plugs or screw terminals
Integrated bus terminating resistor (switchable)
CAN bus-specific status indication with 2 LEDs on the internal (Customer Unit) and external
(Technology Unit) technology option
DEVICE or FI-specific status indication with 2 LEDs on the internal (Customer Unit) and external
(Technology Unit) technology option
CAN interface as per specifications 2.0A and 2.0B
Up to four 24V inputs and two 24V outputs are integrated into the bus module
Direct connection of up to 4 sensors and 2 activators via M12 round plug connectors on the SK TU4-
CAO-M12(-C) version. Visualisation of signal status via LEDs
Transmission and selection of process and parameter data
CAN Bus gateway solution → up to 4 frequency inverters can be connected to a CANopen bus
module. Each FI is allocated its own SDO channel
Up to 63 nodes (e.g. CANopen bus modules) on a single bus. With this, up to 252 frequency inverters
can be operated on a single bus by means of gateway.
Support of 11 bit and 29 bit identifiers by the technology modules
Supports DS-301 communications profile and DS-402 drive profile for “Velocity Mode” (with
Technology Units)
Programming of all frequency inverter parameters using SDO
Dynamic PDO mapping (5 TxPDOs and 5 RxPDOs) for great reduction in the number of parameters
Heartbeat and node-guarding monitoring functionality
Interface (RS232/RS485) for parameter access by means of the SK PAR-3H manual control unit or
NORDCON software via RJ12 connector (Except for SK CU4-CAO. Here parameter access via the
SK 200E frequency inverter is possible)
Integrated EEPROM with extensive bus-specific parameter database with parameter editing facilities via:
- ParameterBox and Nordcon: direct access / direct saving
- CANopen Bus Saving via - Index 0x1010 sub0 Store Parameters,
- Index 0x1011 sub0 Restore default Parameters
Available as versions for installation in the inverter (IP20) or in a separate housing (optionally IP55 / IP66)
1.2 Delivery
Check the equipment immediately after delivery/unpacking for transport damage such as deformation or
loose parts.
If there is any damage, contact the carrier immediately and implement a thorough assessment.
Important! This also applies even if the packaging is undamaged.